Siemens SICHARGE UC 150 UL Installation And Operation Manual page 59

Plug-in dispenser
Table of Contents

Advertisement

Connecting the Ethernet or fiber-optic cable
NOTICE
Network connection
The SICHARGE UC devices form a closed network.
Do not establish a connection to other networks and devices.
Observe the specifications for the routing of Ethernet cables in the section Location planning
1. Insert the Ethernet cable into the SICHARGE UC dispenser to the right of the DC cables.
2. Insert the RJ45 plug of the Ethernet cable into a free connection of the SICHARGE UC dispenser
Ethernet switch -A2.
Observe the specifications for the routing of fiber-optic in the section Location planning
1. Insert the fiber-optic plug (SC socket type) into the SICHARGE UC dispenser to the right of the DC cables.
2. Insert the of the fiber-optic cable into a free connection of the SICHARGE UC dispenser Ethernet switch -A2
(Port 1 or Port 4).
Note
Assembling the industrial Ethernet connector
Follow the instructions of the connector manufacturer to assemble the industrial Ethernet connector.
Cable routing considerations
All circuits (incoming AC power wiring, DC wiring to dispensers and communications wiring) should
be ran in separate conduit runs until reaching the cable gland plates.
Fastening the cable
Ensure that the communication cable is not making contact with any other wires.
Connection of additional SICHARGE UC dispensers
The Ethernet connection is looped through to connect additional SICHARGE UC dispensers to the same
SICHARGE UC charging station. This is shown as item s in the "Communication connection" (Figure 6-3).
To do this, perform the sequence shown above to connect the Ethernet cable.
Installation and Operations Manual | SICHARGE UC 150 UL Plug-in Dispenser
(Page
(Page
37).
37).
59