Hitachi Relion 670 Series Commissioning Manual page 65

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
LON communication setting parameters (Table 16) and LON node information parameters (Table 17) can
only be set via the LON Network Tool (LNT).
Some of these parameters can be viewed on the local HMI under Main menu /Configuration /
Communication /Station communication /Port configuration /SLM optical LON port /LONGEN:1 .
Table 16:
Parameter
DomainID
SubnNetAddr*
NodeAddr*
*Can be viewed on the local HMI
Table 17:
Parameter
NeuronID*
Location
*Can be viewed on the local HMI
ADE settings are available on the local HMI under Main menu /Configuration /Communication /
Station communicaton /LON /ADE:1
Table 18:
Name
Operation
TimerClass
LON commands are available on the local HMI under Main menu /Configuration /Communication /
Station communication /Port configuration /SLM optical LON pot /Service Pin Messae /Generate
service pin message
Table 19:
Command
ServPinMess
Line distance protection REL670
Commissioning manual
LON communication setting parameters
Range
Default
0
0
0 - 255
0
Step: 1
0 - 127
0
Step: 1
LON node information parameters
Range
Default
0 - 12
Not loaded
0 - 6
No value
ADE Non group settings (basic)
Values (Range)
Disabled
Enabled
Slow
Normal
Fast
LON commands
Command description
Command with confirmation. Transfers the node address to the LON Network Tool.
© 2017 - 2023 Hitachi Energy. All rights reserved
Establishing connection and verifying the LON communication
Unit
Parameter description
-
Domain identification number
-
Subnet address
-
Node address
Unit
Parameter description
-
Neuron hardware identification number in hexadecimal
code
-
Location of the node
Unit
Step
-
-
-
-
Default
Description
Disabled
Operation
Slow
Timer class
Section 7
M11643-1 v4
59