Hitachi Relion 670 Series Commissioning Manual page 125

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
Test point
P6
P7
P8
P9
P10
P11
P12
P13
P14
Table 36:
Test point
P15
P16
P17
P18
P19
P20
P21
P22
P23
P24
P25
P26
P27
P28
4.
Change the magnitude and angle of three phase voltages to achieve the impedances at test points
P1, P2,...., P28.
5.
For test points P1 to P14, observe the operation value for the signal ZOUT and compare the
operation value with the set value.
6.
For test points P15 to P28, observe the operation value for the signal ZIN and compare the
operation value with the set value.
Testing the power swing detection logic ZMBURPSB (68)
Preconditions
Line distance protection REL670
Commissioning manual
R
0.8 * (R1FInFw + ∆Fw)
R1FInFw + ∆Fw
0.0
-(0.8 * R1LIn + R1FInRv +
∆Rv)
-0.8 * (R1FInRv + ∆Rv)
-RLdOutRv
-R1FInRv + ∆Rv
-0.8 * (R1FInRv + ∆Rv)
-(R1FInRv + ∆Rv)
Testing points to measure the inner boundary
R
0.0
0.8 * R1LIn + R1FInFw
0.8 * R1FInFw
RLdInFw
R1FInFw
0.8 * R1FInFw
R1FInFw
0.0
-0.8 * R1LIn + R1FInRv
-0.8 * R1FInRv
-RLdInRv
-R1FInRv
-0.8 * R1FInRv
-R1FInRv
© 2017 - 2023 Hitachi Energy. All rights reserved
Testing functionality by secondary injection
X
Comment
-0.8 * (R1FInFw + ∆Fw) *
tan (ArgLd)
-0.8 * X1OutRv
-X1OutRv
-0.8 * X1OutRv
-0.8 * (R1FInRv + ∆Rv) *
tan (ArgLd)
0.0
0.0
If OperationLdCh = Off
0.8 * (R1FInRv + ∆Rv) * tan
(ArgLd)
0.8 * X1OutFw
X
Comment
X1InFw
0.8 * X1InFw
(0.8 * R1FInFw + ∆Fw) *
tan (ArgLd)
0.0
0.0
If OperationLdCh = Off
-(0.8 * R1FInFw + ∆Fw) *
tan (ArgLd)
-0.8 * X1InRv
-X1InRv
-0.8 * X1InRv
-(0.8 * -R1FInRv + ∆Rv) *
tan (ArgLd)
0.0
0.0
If OperationLdCh = Off
(0.8 * -R1FInRv + ∆Rv) *
tan (ArgLd)
0.8 * X1InFw
Section 11
GUID-E19CFFAA-3853-4895-A149-32F6E78B2C69 v1
119