Siemens SIMOCRANE Operating Instructions Manual page 125

Energy storage system management v01.01
Table of Contents

Advertisement

Bit 16
Acknowledgement
Cause
Remedy
Bit 17
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 18
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 19
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 20
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 21
Message class
Component
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE
Internal CAT-0 Stop detected
ETechAcknowledge
Internal CAT-0 stop request (see following message)
Clarify the cause (see following faults) and acknowledge the fault
License insufficient
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
An invalid license has been detected
Use a valid license
BMS voltage doesn't match measured battery voltage
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
BMS battery voltage does not match measured value
Clarify the cause of the discrepancy
Measured Battery voltage < MIN
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
Battery undervoltage
Clarify the cause of the undervoltage
External application CAT-0 detected
Fault
Master PLC
Shutdown routine 3
ETechAcknowledge
External application emergency stop detected
Clarify the cause and acknowledge the fault provided no safety hazard exists
System Check failed. No valid start config
Fault
Internal SIMOCRANE ESSM Vx.x
Diagnostic system
7.3 Faults
123