System Config; Mode Control - Siemens SIMOCRANE Operating Instructions Manual

Energy storage system management v01.01
Table of Contents

Advertisement

Diagnostic system
7.2 Warnings
Bit 2
Acknowledgement
Cause
Remedy
Bit 3
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 4
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 5
-
Bits 6-31
-
7.2.2

System Config

Bits 0-31
-
7.2.3

Mode Control

Bit 0
Message class
Component
100
DC-Link Voltage setpoint in mode PS < 500.0 V -> Limited to 500.0 V
Self-acknowledging
A DC link voltage setpoint < 500 V has been detected
Enter a voltage setpoint > 500 V
DC-Link Voltage setpoint in mode MAN/BS < 330.0 V -> Limited to 330.0 V
Warning
Setpoint input mode: "Black Start"/"Manual"
Limitation of setpoint to 330.0 V
Self-acknowledging
A DC link voltage setpoint < 330 V has been detected
Enter a voltage setpoint > 330 V
DC-Link Voltage setpoint in mode MAN/BS > 810.0 V -> Limited to 810.0 V
Warning
Setpoint input mode: All
Limitation of setpoint to 810.0 V
Self-acknowledging
A DC link voltage setpoint > 810 V has been detected
Enter a voltage setpoint < 810 V
Reserved for 250 kW devices
-
Spare
-
Spare
-
Manual Start selection blocked; ESS is not OFF
Warning
Control
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE

Advertisement

Table of Contents
loading

Table of Contents