4.3.2. Simple copying function

The data stored in the memory A, B or C of Remote Keypad can be copied to the inverter's memory
with simple operation of two keys to select one of the memories A, B and C. Use this function to set
the same parameters to more than two inverters. Remote Keypad can not copy parameters to from
one inverter to another inverter of a different series. What differs from the "Copying function" in
Section 0 is the key operation and the contents of parameters to be copied are the same for both
functions. It is impossible to copy data from the inverter's memory to a memory of Remote Keypad
in this function.
N.B.: To copy data to the inverter's memory, do it when the inverter has stopped. If you copy data
to the inverter while the inverter is running, some of the parameters may fail to be copied.
Operating procedure
Key
LED indication
RUN
"copy"
A
"a-in"
"a-in"
ENT
"f_ _ _"
"c0mp"
"end"
"_ _ _ _"
(4 digits)
"_ _ _ _"
ENT
"copy"
- If the [ESC] key is pressed, Remote Keypad re
- When the memory protection function is actuated, Remote Keypad inhibits copying data with " prot " appearing in
the display window.
- If there is no data in memory A of Remote Keypad upon selection as data to copy from, the display shows " err.a "
which means copying data is impossible. (When the memory B or C is selected in the same condition, " err.b " or
" err.c " appears in the display window.)
- In " a-in" ," b-in" and " c-in" , when the data of the inverter increases by the upgrade, the data not included
in memory A, B, and C is not changed.
The same operation as above can also be used to copy data from memory B or memory C of Remote
Keypad to the inverter.
STOP
ENT
B
< Selecting and entering a memory to copy its data >
Press the key corresponding to the memory selected to copy data from, while
"copy" is being displayed.
[A] key: To copy data from memory A to the inverter's memory.
[B] key: To copy data from memory B to the inverter's memory.
[C] key: To copy data from memory C to the inverter's memory.
When memory A is selected to copy its data to the inverter's memory for example,
the display changes from "copy" to "a-in" (copying data from memory A to
inverter's memory).
< Executing copy function >
After selecting the memory to copy from (to inverter, Example: select "a-in"),
press the [ENT] key, and start copying. Then the display shows "f_ _ _". This is
the parameter title of the parameter being copied now. If Remote Keypad is unable
to copy the selected parameter, the display shows the parameter title flashing in the
display window. To continue copying, press [ENT] key.
< Completion of copying function >
After completing the copy operation, "c0mp" begins to flash to indicate that
Remote Keypad is comparing two sets of parameters. (Refer to "comparing
function" in section 4.3.3). When the comparison is end, it displays CRC code "_ _
_ _" (4 digits in hexadecimal number) of memory data for error detection after
displaying "end". If the parameters are different, the comparison interrupts and
the parameter title number flashes on display. To continue comparison for next
parameter, press [ENT] key. When the comparison is end, the CRC codes of
original and copied memory data for error detection flash alternately after
displaying "end".
The CRC code "_ _ _ _" (4 digits in hexadecimal number) changes depending on
the data condition.
< Ending copying >
Press the [ENT] key and the indication in the display window returns to "copy".
turns to previous status (except when executing).
Since the [ A ], [ B ], and [ C ] keys are provided to be used
exclusively for the simple copying function, those keys cannot
ENT
C
be used for other functions.
Key operation and description
11
E6581277

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rkp002z

Table of Contents