UPS2000-G-(6 kVA-20 kVA)
User Manual

4.6.3.5 Restoring Factory Settings

You can restore factory settings after the inverter shuts down.

4.6.4 Control

On the Main Menu screen, select Control, and press
displayed.
Startup
The Startup menu allows you to start the inverter.
Figure 4-44 Startup screen
Shutdown
The Shutdown menu allows you to shut down the inverter.
Issue 21 (2022-10-13)
Table 4-36 Shallow Discharge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
Item
Description
Test
Determine whether to
notificati
periodically send shallow
on
discharge test notifications.
The values include Disabled
and Enabled. The default
value is Disabled. If the
value is Enabled, the
system sends shallow
discharge test notifications.
The parameter is
configurable in any mode.
Time
Set the time interval for
interval
shallow discharge tests. The
parameter is configurable in
any mode.
Discharge
Set the proportion of the
ratio
discharge capacity to the
total discharge capacity. The
parameter is configurable in
any mode.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
Default Value
Value Range
Disabled
Disabled,
Enabled
60 days
30–90 days
20%
10%–50%
. The Control screen is