I
Transferring the UPS That Has Generated
an Alarm to Normal Mode and Clearing the
Procedure
Step 1 Press the INFO button to confirm that the alarm is generated for the bypass
power supply.
Step 2 Press the OK button for 5 seconds or enter the control screen to start the inverter.
Step 3 Verify that the alarm is cleared and the alarm tone disappears.
----End
Issue 21 (2022-10-13)
Copyright © Huawei Technologies Co., Ltd.
I Transferring the UPS That Has Generated an Alarm
to Normal Mode and Clearing the Alarm Tone
Alarm Tone
164