LMV5x
Terminal
Pin 1
Protective Earth Ground
Low Oil Pressure Switch
X5-01
Pin 2
Opens on low oil pressure (OilPressureMin)
Pin 3
Line
Pin 1
Protective Earth Ground
High Oil Pressure Switch
X5-02
Pin 2
Opens on high oil pressure (OilPressureMax)
Pin 3
Line
Burner ON / OFF Switch
Pin 1
If deactivated, ON / OFF via ModBus or AZL (InputController)
Floating-Bumping Drive to Low Fire
Pin 2
modulation with RWF40 in floating bumping mode, or
power to achieve Stage 3 with staged oil (Operation Mode)
X5-03
Floating-Bumping Drive to High Fire
Pin 3
modulation with RWF40 in floating bumping mode, or
power to achieve Stage 2 with staged oil (Operation Mode)
Pin 4
Line
Start Release Oil (StartReleaseOil)
Pin 1
Typical: Atomizing Media Pressure Switch, closes on pressure
Pin 2
Line
X6-01
Start Release Heavy Oil
Pin 3
Powered to release stages of Heavy Oil (StartRelease)
Pin 4
Line
Pin 1
Protective Earth Ground
Pin 2
Neutral
X6-02
Oil Pump Motor Starter (also known as Magnetic Clutch)
Pin 3
(OilPumpCoupling, IgnOilPumpStart, IgnOnTmeOilPump)
Pin 1
Protective Earth Ground
Pin 2
Neutral
X6-03
Oil Outdoor Safety Valve Energizes phase 21
Pin 3
Typical: Atomizing Air Compressor Motor Starter
Pin 1
Protective Earth Ground
X7-01
Pin 2
Neutral
Pin 3 Main Oil Valve V2 Used for staged combustion on oil
Pin 1
Protective Earth Ground
Pin 2
X7-02
Neutral
Pin 3 Main Oil Valve V3 Used for staged combustion on oil
Pin 1
Protective Earth Ground
CPI Oil Typical, Configurable for:
X7-03
deactivated, Start RelGas, CPI Oil, CPI Gas, or CPI Gas+OIL
LMV52
Pin 2
Note: CPI, Closed Position Indicator = POC, Proof Of Closure
Only
(StartReleaseGas)
Pin 3
Line
LMV5 QSG Rev 4
Figure 3-2.3 X5, X6, and X7
Description / Notes
Sec 3
(related Parameter)
(LC_OptgMode)
(LC_OptgMode)
Pg 8
www.scccombustion.com
Type
Rating
PE
N/A
Programable
1.5 mA, 120V
Input
Line
500 mA, 120V
PE
N/A
Programable
1.5 mA, 120V
Input
Output
500 mA, 120V
Programable
1.5 mA, 120V
Input
Line
500 mA, 120V
Programable
1.5 mA, 120V
Input
Output
500 mA, 120V
Programable
1.5 mA, 120V
Input
Line
500 mA, 120V
PE
N/A
N
Programable
1.6 A, 120V
Output
PE
N/A
N
Output
1.6 A, 120V
PE
N/A
N
Output
1.6 A, 120V
PE
N/A
N
Output
1.6 A, 120V
PE
N/A
Programable
1.6 mA, 120V
Input
Line
500mA, 120V