Siemens LMV5 Quick Start Manual page 112

Hide thumbs Also See for LMV5:

Advertisement

Menu Path
Parameter
LC_OptgMode
Params & Display>
System Config
Ext Inp X62 U/I
TL_Thresh_Off
TL_SD_On
Params & Display>
System Config>
Temp Limiter
Sensor Select
MeasureRangePtNi
MeasureRangePtNi
O2Ctrl/LimitrGas or
O2Ctrl/LimitrOil
Params & Display>
System Config
LC Analog Output
allowed Pot.Diff
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Current operating mode of the LMV.
Can also be changed at: Params&Display>Loadcontroller>Configuration>LC_OptgMode .
U
Note - if "Load Controller not active..." message was seen under:
Params & Display > Load Control > LC_OptgMode , adjust this parameter
to some internal mode before returning to the Load Controller menu.)
See: Params & Display > LoadController > Configuration > Ext Inp X62 U/I
See: Params & Display > LoadController > Controller Params > Temp Limiter > L_Thresh_Off
See: Params & Display > LoadController > Controller Params > Temp Limiter > TL_SD_On
See: Params & Display > LoadController > Configuration > Sensor Select
See: Params & Display > LoadController > Configuration > Inp1/2/4Sel
See: Params & Display > LoadController > Configuration > Inp1/2/4Sel
S
See: Params & Display > O2 Contr/Guard > GasSettings > OptgMode
See: Params & Display > LoadController > Configuration > Analog Output > OutValueSelection
Sets the allowable differernce between channels A and B of the Actuator's Potentiometer.
Range = 10 to 15. Def / Typ = 10
Sec 4 Pg 56
Descriptions / Notes
All
60-62
All
www.scccombustion.com