Selection menus in the AZL5
Activation of Modbus operation
Slave address
Transmission parameters
Transmission rate
Parity
Timeout communication failure
Local «-» Remote mode
Remote mode
LMV5 QSG Rev 4
Activation takes place via menu
«Operation» «OptgModeSelect» «GatewayDDCon».
Having made the selection, the menu item can be quit via ESC. The setting is retained until
«Operation» «OptgModeSelect» «GatewayDDCoff» is selected via the AZL... menu.
When «GatewayDDCon» is activated, plant operation and diagnostics via the AZL... are still
possible.
Deactivation takes place via menu
«Operation» «OptgModeSelect» «GatewayDDCoff».
Selection is made via menu
«Params & Display» «AZL» «Modbus» «Address».
According to Modicon specifications, addresses between 1...247 can be selected. The
slave address is filed in nonvolatile memory of the AZL...
The setting is made via menu
«Params & Display» «AZL» «Modbus» «Baud Rate»
There is a choice of 9600 bit/s or 19200 bit/s.
Using the AZL... menu
«Params & Display» «AZL» «Modbus» «Parity», parity can be set to
even
or
odd
.
«
»
«
»
When there is no Modbus communication, this timeout defines the period of time on com-
pletion of which the AZL... changes automatically from Remote to Local.
The setting is made via menu
«Params & Display» «AZL» «Modbus» «Downtime».
This setting defines whether the AZL... shall work in Local or Remote mode.
Display of «Remote Auto», «Remote On», «Remote Off» mode. A change can only be
made via Modbus.
Sec 8 Pg 12