Siemens LMV5 Quick Start Manual page 200

Hide thumbs Also See for LMV5:

Advertisement

F
unction
Address
Number
of
words
03/04
35
1
Coding: 0
inactive 1
active
B15
B14
B13
B8
Safety loop
B9
B10
Pressure switch-min-gas
B11
Pressure switch-max-gas
B12
B13
LP
B14
Start release oil
B15
Heavy oil immediate start
Function
Address
Number
of
words
03/04
37
1
Coding: 0
inactive 1
active
B15
B14
B13
B8
Fuel valve SV oil
B9
Fuel valve V1 oil
B10
Fuel valve V2 oil
B11
Fuel valve V3 oil
B12
Fuel valve SV gas
B13
Fuel valve V1 gas
B14
Fuel valve V2 gas
B15
Fuel valve PV gas
Function
Address
Number
of
words
R 03/04
38
1
W 06/16
R 03/04
39
1
W 06/16
R 03/04
40
1
R 03/04
41
1
W 06/16
LMV5 QSG Rev 4
Data designation
Inputs
B12
B11
B10
B9
B8
Data designation
Outputs
B12
B11
B10
B9
B8
Data designation
Program stop
Operating mode with load controller
Selection of manual or automatic operation
Modbus mode: Local / Remote
Sec 8 Pg 6
Acces
Data type /
s
coding
R
U16
B7
B6
B5
B4
B0
Controller ON/OFF
B1
Fan contactor contact
B2
Fuel selection oil
B3
Fuel selection gas
B4
B5
Pressure switch-max-oil
B6
Pressure switch-min-oil
B7
Pressure switch – valve proving
Acces
Data type /
s
coding
R
U16
B7
B6
B5
B4
B0
Alarm
B1
B2
B3
B4
Ignition
B5
Start signal / DW valve
B6
Fan
B7
Oil pump / magnetic coupling
Access Data
Data type /
format
coding
R/W*
U16
0=deactivated
1=24 PrePurgP
2=32 PrePFGR
3=36 IgnitPos
4=44 Interv 1
5=52 Interv 2
6=72 PostPPos
7=76 PostPFGR
R/W*
U16
0=ExtLR X5-03
1=IntLR
2=IntLR Bus
3=IntLR X62
4=ExtLR X62
5=ExtLR Bus
R
U16
0=automatic
1=burner on
2=burner off
R/W
U16
0 = Local
1 = Remote
www.scccombustion.com
Range
Updating
rate
-
Medium
B3
B2
B1
B0
Range
Updating
rate
-
Medium
B3
B2
B1
B0
Range
Updating
rate
0...7
Slow
0...5
Slow
0...2
Fast
0...1
Slow