Fastening On A Level Substructure - Siemens FDA241 Mounting & Installation

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

3.2
1
Using the drilling template
Building Technologies
Fire Safety

Fastening on a level substructure

A drilling template is punched in the inner packaging of the aspirating smoke
detector packaging.
The punched symbol in the center of the packaging indicates the airflow direction
(air inlet and air outlet).
The mounting holes in the back box are not symmetrical, so use the drilling
template.
2
 4 screws with a shaft diameter of 5...6 mm and a head diameter of 8...10 mm
are available.
 A suitable tool for drilling and screwing is available.
 The housing cover is removed and the cable loosened.
 The product must be installed on a level, non-combustible base.
1. Use the unfolded packaging as the drilling template.
Note the arrow symbol for the direction of the pipe connections (step 3).
2. Drill the mounting holes.
3. If necessary: Use suitable dowels.
firealarmresources.com
Mounting
Fastening on a level substructure
3
4x
A6V10345654_h_en_--
3
17
2015-05-29