System Functions; Monitoring - Huawei FusionModule500 Smart User Manual

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
The NetEco can manage the infrastructures of a single data center or of data
centers in various areas in a centralized manner.
The ECC800-Pro manages the real-time status, alarms, and configuration
information about the devices inside the smart module. It also provides a
graphical user interface (GUI) for ease of operating and maintaining devices inside
the smart module.
Figure 3-6 System network diagram

3.4.2 System Functions

3.4.2.1 Monitoring

Issue 02 (2021-06-30)
Temperature and humidity monitoring: Detects and collects statistics on the
ambient temperature and humidity inside the smart module; provides real-
time alarm signals.
Water leakage monitoring: Detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
Smoke monitoring: Detects smoke in the smart module and provides real-
time alarm signals.
Power distribution monitoring:
a.
(In the intelligent power distribution scenario) Monitors the general
mains input voltage, frequency, current, and power, as well as the UPS
input voltage, frequency, current, and so on.
b.
(In the non-intelligent power distribution scenarios) Monitors the UPS
input voltage, frequency, current, and so on.
Smart cooling product monitoring:
a.
Monitors the supply and return air temperatures in real time.
b.
Allows you to set the return air temperature setpoint for a single product.
c.
Monitors and displays the fan speed, and displays the running
percentage.