Huawei FusionModule500 Smart User Manual page 117

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
To learn the mapping between the saturation pressure and the saturation
temperature of the R410A refrigerant, see
Table 5-2 Mapping between the saturation pressure and the saturation
temperature for R410A
Saturation
Temperatu
re (°C)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Users include admin (preset password: Changeme) and operator (preset
password: Changeme). To enter the diagnostic mode, log in as user admin.
Issue 02 (2021-06-30)
Gauge
Pressure
(MPa)
0.7
0.73
0.75
0.78
0.81
0.84
0.87
0.9
0.93
0.96
0.99
1.02
1.05
1.09
1.12
1.16
1.19
1.23
1.27
NO TE
1 MPa ≈ 10 bar ≈ 145 psi ≈ 10.2 kgf/cm
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Table
5-2.
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
19
1.31
20
1.35
21
1.39
22
1.4
23
1.47
24
1.51
25
1.56
26
1.60
27
1.65
28
1.69
29
1.74
30
1.79
31
1.84
32
1.89
33
1.94
34
1.99
35
2.04
36
2.1
37
2.15
2
5 Power-On Commissioning
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
38
2.21
39
2.27
40
2.33
41
2.39
42
2.45
43
2.51
44
2.57
45
2.63
46
2.7
47
2.76
48
2.83
49
2.9
50
2.97
51
3.04
52
3.11
53
3.19
54
3.26
55
3.34
-
-
108