Access Modular Controller 2
4.13

Connecting analog input devices

The AMC2 has eight analog inputs, for example, for potential-free lock mechanisms, or to
detect whether a lock is closed or open. The inputs will be connected to the 2-pin pluggable
screw connectors: S3, S4, S8, S9, S15, S16, S20 and S21.
For more information on these connections, refer to Connecting diagrams, page 45 .
Notice!
Risk of damage to equipment
i
Do not connect external power supply to the AMC2 inputs.
When you connect an AMC2 relay output to an input, use the relay output in floating mode -
refer to Connecting relay outputs, page 29 .
Figure 4.22: Location of the analog input connectors
The AMC2 can also detect the wiring conditions 'short circuit' and 'broken', and hence trigger
an alarm if the appropriate devices are connected.
Figure 4.23: Circuit diagram
Bosch Security Systems B.V.
2
3
4
5
6
1
1
AMC2 analog input
3
Resistor parallel (R
5
Broken wire
)
P
Installation manual
2
Monitoring / door contact
4
Resistor serial (R
)
S
6
Short circuit
Installing | en
31