Chapter 5 - Mechanical installation
5.3.4
Cable duct material
5.4
Preparing the floor
Condition of the floor
5.5
Fixing the cabinet to the floor
5-2 (4)
Cable ducts should be of non-flammable material with non-abrasive
surface.
All cable entries and exits should be protected to prevent dust, humidity
and animals entering into the drive.
■
Must support the weight of the cabinet
■
Overall incline across 5 m must not exceed 5 mm
■
Even
■
Non-flammable, smooth and non- abrasive
■
Protected against humidity diffusion
The cabinet provides a hole in each corner of the base for floor fixings. The
holes are accessible from the outside.
Floor fixings are not supplied. Anchor bolts as illustrated, or screws and
nuts of size M20 are recommended.
Fig. 5-1