GE PACSystems RX3i User Manual page 57

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Status/Alarm Timing
GFK-2749
Timing A – The PSM buffers an entire power line cycle and takes 11ms to perform
calculations on the waveforms. The new status bits are available to the application code
after the next PLC input data scan.
Total latency = 1-cycle + 11ms + (0 to PLC scan time)
Update rate = 1-cycle or the PLC scan rate (whichever is longer)
Timing B – The PSM updates this information every 100ms. The new status bits are
available to the application code after the next PLC input data scan.
Update rate = 100ms or the PLC scan rate (whichever is longer)
Timing AB – AllGridAlarmsOK follows the timing of the alarm that causes it to be cleared
or set.
Chapter 3 Configuration and Data Transfer