GE PACSystems RX3i User Manual page 56

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

3
%I Bit
Offset
54
GRID 1 ReversPwrAlarm
55
GRID 1 OverCurrAlarm
56
GRID 1 OverVoltAlarm
57
GRID 1 VIImbalanceAlarm
58
GRID 1 UnderFreqAlarm
59
GRID 1 OverFreqAlarm
60 - 64
Reserved
65
GRID 2 ClampedFreq:
66
GRID 2 ClampedInput:
67
GRID 2 MixedPolarity
68
GRID 2 VoltPhSeqAlarm
69
GRID 2 UnderVoltAlarm
70
GRID 2 ReversPwrAlarm
71
GRID 2 OverCurrAlarm
72
GRID 2 OverVoltAlarm
73
GRID 2 VIImbalanceAlarm
74
GRID 2 UnderFreqAlarm
75
GRID 2 OverFreqAlarm
76 – 80
Reserved
3-12
Definition
PACSystems* RX3i Power Sync and Measurement System – February 2013
Value
0 = OK
1 = ANSI 32 Alarm
0 = OK
1 = ANSI 50 Alarm
0 = OK
1 = ANSI 59 Alarm
0 = OK
1 = ANSI 60 Alarm
0 = OK
1 = ANSI 81U Alarm
0 = OK
1 = ANSI 81O Alarm
0 = OK
1 = Line Frequency outside the
range (30 - 70 Hz)
0 = OK
1 = some inputs have signal
clamped
0 = OK
1 = At least one phase PT/CT has
wrong polarity
0 = OK
1 = ANSI 47 Alarm
0 = OK
1 = ANSI 27 Alarm
0 = OK
1 = ANSI 32 Alarm
0 = OK
1 = ANSI 50 Alarm
0 = OK
1 = ANSI 59 Alarm
0 = OK
1 = ANSI 60 Alarm
0 = OK
1 = ANSI 81U Alarm
0 = OK
1 = ANSI 81O Alarm
Status/Alarm
Alarm
Timing
Availability
A, B, AB: See
"Status/Alarm
ø
1
Timing" on page
3-13
B
B
B
B
B
B
A
A
B
B
B
B
B
B
B
B
B
GFK-2749
3
ø
3