1-14
Example: Angle Delay ≤ (Phase_Shift_Thr - 2º)/2
Phase_Shift_Thr = 10º
Breaker Delay = 200ms
Grid 1 Frequency = 60.00Hz
Grid 2 Frequency = 60.01Hz
ΔF (slip frequency) = 0.01Hz
Angle Delay = (360º x 0.01Hz x 0.200sec) = 0.72º
PhaseShiftOK = On @ 0.72º {Angle Delay}
PhaseShiftOK = Off @ -2.72º {-(Angle Delay + 2º)}
If Sync is requested while PhaseShiftOK = On, then CloseRelayOK will be set to On
for the Angle Delay + 24 cycles. At ΔF = 0.01HZ and 60Hz, the PhaseShiftOK window
is 200ms (0.72⁰) + 400ms = 600ms.