Demounting; Electric Connection; Procedure To Connect The Lines To X1S1 - Bosch rexroth IndraControl VAC 08.1 Operating Instructions Manual

Table of Contents

Advertisement

IndraControl VAC 08.1 CDI+ Splitter
The distances of the mounting holes are listed in
the CDI+ splitter – Rear view" on page
Use two M5 screws to fasten the CDI+ splitter.
2. Fixing the cables
Unfixed cables are not permitted. Therefore, an appropriate fixing (e. g. in-
stallation in a cable channel) and a strain relief of the cables is required.

10.4 Demounting

1. Disconnect the CDI+ splitter from voltage.
2. Remove all connected cables including the cable at the function earth con-
nection.
3. Loosen both screws used to attach the CDI+ splitter box to the rear panel.
4. Lift the CDI+ splitter vertically and remove it from the rear panel.

10.5 Electric connection

10.5.1 Procedure to connect the lines to X1S1

Connect the lines as described in the following:
1. Strip the lines to a length of 9 mm.
2. Loosen the spring by pressing it using the screwdriver ①.
3. Put the line into the clamping point ②.
4. Fix the line by removing the screwdriver.
Fig. 10-5: Connecting the lines at X1S1
Bosch Rexroth recommends a 0.4 mm x 2.5 mm x 80 mm screwdriv-
er.
Mounting, demounting and electric installation
16.
1 1
2
R911400465_Edition 01 Bosch Rexroth AG
fig. 10-3 "Dimensions of
17/33