Huawei PDU8000 User Manual page 57

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Main
Menu
Issue 01 (2016-02-27)
Second-l
Third-Level/Fou
evel
rth-Level Menu
Menu
System
undervolt
age
Undervol
tage
ack.time
(s)
Overload
(%)
Overload
ack.time
(s)
Overfreq
uency
(Hz)
Overfreq
uency
ack.time
(s)
Upper
load
current
threshold
(%)
Lower
Load
current
threshold
(%)
Three-ph
ase load
imbalanc
e (%)
Settings Wizard
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Function Description
Specifies the lower alarm
threshold in relative to the
rated voltage. The value
ranges from 75 to 95.
Specifies the duration for
confirming an undervoltage
alarm. The value ranges
from 1 to 10.
Specifies the overload alarm
threshold in relative to the
rated load. The value ranges
from 100 to 120.
Specifies the duration for
confirming an overload
alarm. The value ranges
from 1 to 10.
Specifies the overfrequency
alarm threshold in relative to
the rated frequency. The
value ranges from 1 to 10.
Specifies the duration for
confirming an overfrequency
alarm. The value ranges
from 1 to 10.
Specifies the upper alarm
threshold in relative to the
rated current. The value
ranges from 80 to 100.
Specifies the lower alarm
threshold in relative to the
rated current. The value
ranges from 30 to 80.
Specifies the alarm threshold
in relative to the balanced
three-phase current. The
value ranges from 5 to 50.
Enables you to set language,
time, network, and system
parameters.
7 User Interface
Preset
Value
85
5
100
1
1.5
5
80
60
15
N/A
51