Siemens SIMATIC S7-1500 System Manual page 106

Drive controller
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Interfaces X122/X132 (SINAMICS Integrated)
The digital inputs and digital inputs/outputs are by default assigned to the drive (CU DO1).
You can use frame interconnection so that these digital inputs and digital inputs/outputs can
also be used by the CPU. To do so, you configure a frame 39x for automatic speed control.
Table 7- 5
Scope of input/output data of the digital inputs and digital inputs/outputs X122/X132
Frame
Inputs
390
4 bytes
391
14 bytes
392
30 bytes
393
42 bytes
394
6 bytes
You can find a description of the control and feedback interface of the frames in the
SINAMICS S120/S150 List Manual
(https://support.industry.siemens.com/cs/de/de/view/109763271/en), function diagram 2422
and 2495 to 2500. There you will also find a description of other frames that are not the
focus with the SIMATIC Drive Controller.
See also SINAMICS G/S FAQ: Configuration of standard frames in the TIA Portal
(https://support.industry.siemens.com/cs/ww/en/view/82841762)
STEP 7 assigns the addresses automatically. You can change the addresses in the
hardware configuration of STEP 7, that is, freely assign the start address. The addresses of
the channels are based on the start address.
You can, for example, find the assigned addresses:
● In the device view of the SINAMICS Integrated, in the Inspector window, on the General
tag under frame configuration
● In the network view when you select the network; the addresses are then displayed under
Address overview in the Inspector window
SIMATIC Drive Controller
System Manual, 11/2019, A5E46600094-AA
Outputs
Use of Integrated/CU320-2
4 bytes
No measuring input; DI0 to DI7; DI/DQ8 to DI/DQ15
6 bytes
Two measuring inputs; DI0 to DI7; DI/DQ8 to DI/DQ15
6 bytes
Six measuring inputs; DI0 to DI7; DI/DQ8 to DI/DQ15
8 bytes
8 measuring inputs; DI0 to DI7; DI16, DI17, DI20, DI21, DI/DQ8 to DI/DQ15
(for CU310-2 also: DI18, DI19, DI22, DO16, AI0)
6 bytes
No measuring inputs; DI0 to DI7; DI16, DI17, DI20, DI21, DI/DQ8 to DI/DQ15
(for CU310-2 also: DI18, DI19, DI22, DO16, AI0)
Configuring
7.7 Address space
105