112 en | Specifications and certifications
1-350-99-ttt
COMMUNICATION TROUBLE
3-350-99-ttt
COMMUNICATION TROUBLE
(restoral)
1-354-99-000
FAILURE TO COMMUNICATE
3-354-99-000
FAILURE TO COMMUNICATE
(restoral)
1-371-99-iii
PROTECTION LOOP OPEN
3-371-99-iii
PROTECTION LOOP OPEN
(restoral)
2017.11 | 05 | F.01U.311.207
Contact ID report
(i = input number, 001-004)
(t = trouble type)
Installation and Operation Manual
Conettix Universal Dual Path Communicator
B465 Event
When there is a communication trouble
event, the B465 sends a COMMUNICATION
TROUBLE report. It uses the ttt segment of
the report to identify the technology and
receiver.
ttt = 000, Ethernet IP or Cellular IP to
Primary or Secondary Receiver
(B465 with firmware version 1.##.###
only)
ttt = 001, Ethernet IP to primary
receiver
ttt = 002, Cellular IP to primary receiver
ttt = 003, Ethernet IP to secondary
receiver
ttt = 004, Cellular IP to secondary
receiver
ttt = 010, DNS failure using Ethernet IP
or Cellular IP
(B465 with firmware version 1.##.###
only)
ttt = 011, DNS failure using Ethernet IP
ttt = 012, DNS failure using Cellular IP
When any of the communication trouble
events shown above clears, the B465 sends
a COMMUNICATION TROUBLE Restoral
report.
When there is a communication failure event,
the B465 inserts a FAILURE TO
COMMUNICATE report (Contact-ID 354) at
the top of the report queue. It is the first
report sent when communication restores.
When a report is successfully sent to the
central station receiver (after a
communication failure event), the B465 adds
a FAILURE TO COMMUNICATE Restoral
report (Contact-ID 354) to the report queue.
When a B465 input is open, the B465 makes
an input open trouble event and sends a
PROTECTION LOOP OPEN report.
When a B465 input returns to normal after
being open, the B465 makes an input open
trouble event and sends a, PROTECTION
LOOP OPEN Restoral report.