GE AV-300i User Manual page 68

Hide thumbs Also See for AV-300i:
Table of Contents

Advertisement

An inp 1 scale
An inp 1 filter
An inp 1 lo lim
An inp 1 hi lim
AI 1 offs tune
AI 1 gain tune
An inp 1 mon
An inp 1 output
An inp 1 < thr
An inp 1 offset
An inp 1 gain
The figure below shows the function of the lo and hi lim parameters. The input voltage, after the offset and gain
compensation, supplies on the output a linear value included between lo lim and hi lim. The two parameters can
assume any value with the restriction of:
lo lim lower than hi lim
N
!
OTE
it is important to remember that the hardware configuration on the regulation card has to be
set according to the selected input.
Analog inputs
Analog input 1
Analog input 2
Analog input 3
ON Jumper OFF Jumper
- 10V... +10V
0 – 10V, 0 – 20mA
Ch.1
68
Scale factor of the input.
Time constant of the input filter.
Upper limit of the Block output in count (see figure).
Lower limit of the Block output in count (see figure).
Autotune command for the input offset. Input automatic fine-tuning.
Start ?
Autotune command for the input gain. Conditions containing an
Start ?
offset can be compensated.
Monitor for the Block output value.
Monitor for the threshold compensator state (1 the condition is true)
Monitor for the offset value
Monitor for the gain value
Hi lim
-10V...+10V
input connects a signal with a maximum voltage of +/-10V.
The change in the motor rotation direction is obtained according to the signal polarity.
Input voltage > 10V or >-10V cause saturation of the count value.
on the input it is possible to connect a maximum voltage of +10V or a 0...20mA current signal.
The signal must always have a positive sign, through which, if used as a reference, it
is possible to change the motor rotation direction via AI 1 sgn src.
—————— Function Description ——————
GEH-6641E
Input Voltage
lo lim
Input signal
0-10V
S8 = OFF
S9 = OFF
S10 = OFF
0-20mA
4-20 mA
S8 = ON
S9 = ON
S10 = ON
TAVyS0 6