Fig. 9-5: "Ups General" Tab - Bosch Rexroth IPC 40.2 Project Planning Manual

Table of Contents

Advertisement

IPC 40.2
UPS General
DOK-SUPPL*-IPC*40.2***-PR02-EN-P
After calling up UPS Properties and Maintenance, first, the UPS
General tab is active, with which the basic settings of the starting and run
time behavior of the UPS are specified.
Fig. 9-5:
"UPS General" tab
Note:
To activate parameter modifications the UPS program is
automatically stopped and re-started During this time
(5...10 sec) no monitoring takes place.
COM Port: At this place, the serial communication interface is selected,
to which the UPS is connected. If in BIOS one or more serial interfaces
are deactivated, the remaining interfaces of Windows NT are re-
numbered. Therefore, a new interface must be selected in the
configuration dialog under COM port. If no interface is found during the
starting process of the service, a corresponding dialog is opened and the
service is terminated.
In the range Advanced Controls the following settings are possible:
Shutdown Delay Time: Here, a delay time for the shutdown from 0...45 s
is determined. This is the time the user has to back up his data. After the
expiration of the delay time all application programs are terminated
without safety prompt.
When you determine the Shutdown Delay Time, observe that between
the end of the Shutdown Delay Time and the expiration of the 60
seconds after the power down signal remains enough time to shut down
the operating system (for closing the Windows system files and
generating backups). If the time is too short, the shutdown process is
interrupted, because the UPS interrupts the voltage of the power supply
unit. This can cause a loss of data.
9-5
Software
upsc5-general.BMP