Access Control Device - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Item
E-label
Indicators
Table 3-38
Table 3-38 ETH converter indicators
Indicator
PWR
RUN
ALM

3.3.11 Access Control Device

The aisle access control system applies to contained aisles. It monitors and collects data for
devices and personnel moving into or out of contained aisles. Diverse access control devices
such as the fingerprint and card reader with a keypad, fingerprint and card reader, and card
reader with a keypad are supported.
Issue 06 (2020-01-02)
Specifications
Supported
describes the indicators on the ETH converter.
Color
Name
Green
Power input
status
indicator
Green
Operating
status
indicator
Red
Alarm
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The ETH converter
long intervals
successfully registers with the
ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The communication fails or
short
the ETH converter fails to
intervals
register with the ECC800 (the
indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
3 Device Description