User Manual
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > PLC.
Step 3 Check that Enable PLC Function is Yes. If Enable PLC Function is No, choose Yes from
the drop-down list box, and then click Submit.
Step 4 Check that the emergency fan linkage logic under Logic List is Activate.
Step 5 Enable the AI/DI device.
1.
2.
3.
4.
5.
6.
----End

7.5 Battery Shallow Discharge Test

To facilitate operation and maintenance, a battery shallow discharge test can be configured in
the PLC function.
Prerequisites
Only the UPS2000-G-(6 kVA–10 kVA) and UPS2000-G-3 kVA (dual live wires) support a
battery shallow discharge test on the ECC800.
You need to manually configure the battery shallow discharge test based on requirements.
The system type is FusionModule500.
Issue 06 (2020-01-02)
Choose Monitoring > System > ECC800 > Running Parameters.
Set AI/DI_1 Sensor to Enable. Click Submit to access the AI/DI_1 Port Settings page.
Set AI/DI_1 Sensor Name to NTC sensor.
Check that AI/DI_1 Sensor Type is NTC.
Set AI/DI_1 Power Supply to Yes.
Click Submit.
In this example, the fire emergency fan connects to port AI/DI_1. The actual port prevails.