After the smoke alarm is linked with the alarm beacon, if smoke is detected inside the smart
module, the alarm beacon connecting to the corresponding DO2 port will generate an audible
and visual alarm.
Step 1 Choose System Settings > Alarm Linkage.
Step 2 Select the Multi-Func Sensor device type, and click Confirm.
Step 3 Click Select for Smoke alarm and the Set Dry Contact Outputs page is displayed.
Step 4 Select Device type or Device for Linkage Type.
Step 5 (Optional) Select Multi-Func Sensor1 from the Linked Device list if you have selected
Device for Linkage Type.
Step 6 Set DO2 to Yes and click OK.
----End
Linking the AI/DI Alarm with the Alarm Beacon
After the AI/DI alarm is linked with the alarm beacon, if smoke is detected inside the smart
module, the alarm beacon connecting to the corresponding DO port will generate an audible
and visual alarm.
This section describes how to set an alarm linkage by linking output dry contact of the
AI/DI_1 DI alarm on the AI/DI_1 sensor to the DO2 port.
Step 1 Choose System Settings > Alarm Linkage.
Step 2 Select the ECC800 device type and click Confirm.
Step 3 Click Select for AI/DI_1 DI alarm and the Set Dry Contact Outputs page is displayed.
Step 4 Select Device type or Device for Linkage Type.
Step 5 (Optional) Select ECC800 from the Linked Device list if you select Device for Linkage
Type.
Step 6 Set DO2 to Yes and click OK.
----End

7.3 Fire Linkage

Prerequisites
Context
Issue 06 (2020-01-02)
You have obtained the IP address of the ECC800 as well as the user name and password
used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800 is prepared,
and the PC has connected to port WAN_1 on the ECC800.
The system type is FusionModule1000A.
The ECC800 supports the PLC linkage function. It can control the DO output signal by
collecting the signal value. For example, the ECC800 can implement fire linkage by