15 Operating Parameters
15.5 Recording and Reporting
15.5.4
Mains Signalling Voltage
Parameter
MSV active
No. of MSV frequencies
Frequency 1
Frequency 2
Detection threshold
Total recording duration
Pretrigger ratio
15.5.5
Memory Management
Parameter
Event recorder
Measurement recorder
Trend recorder
Fault recorder
Mains signalling voltage recorder
354
Default Setting
Mains signalling voltage measurement
no
1 frequency
216.60 Hz
1060.00 Hz
Mains signalling voltage capture setting
1 % of Udin
75 s
10 %
Default Setting
Memory splitting
1.0 %
35.0 %
(the recording time depends on
the aggregation interval)
47.0 %
(residual storage capacity)
3.0 %
(Numbers of records depends on
the fault-record time)
14%
(Numbers of records depends on
the record time of the mains sig-
nalling voltage)
Setting Range
no
yes
1 frequency
2 frequencies
100 Hz to 3 kHz
100 Hz to 3 kHz
From 1 % to 15 % of Udin
15 s to 120 s in 15-s steps
0 % to 30 % in 5-% steps
Setting Range
1 % to 19 %
33 % to 51 %
Min. 31 %
3 % to 21 %
14 % to 20 %
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018