6.7.3

Starting the Device with the Default IP Address

SICAM Q100 has the following internal default IP address: 192.168.0.55.
If you have entered a custom IP address during device configuration, you can temporarily activate the internal
default IP address of the device if necessary. Proceed as follows:
Hold down the F4 softkey located in the right part of the display side of the device for at least 3 s.
Figure 6-5
When you press the softkey F4, SICAM Q100 will reset and use the default IP address until you have set
a new IP address or switched the device off and on again.
NOTE
Changing the IP address causes the device to reset and the LEDs signal (see chapter 12.3) that the device
was started with the default IP address.
In this case, the parameterized IP address and the default IP address are displayed on the Information tab,
Device information menu item (see chapter 8.2.8)
After starting the device with the default IP address, the factory-set passwords are active, too, (see
chapter 8.3.7.6).
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Location of the Softkey F4 for Activating the Default IP Address
Softkey F4
Default IP Address: 192.168.0.55
Default Subnet Mask: 255.255.255.0