Parameters; Start/Stop/Dir - ABB ACS800 Firmware Manual

Crane control program
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

Parameters

Index
Name/Selection

10 START/STOP/DIR

10.01
EXT1 STRT/STP/DIR
NOT SEL
DI1 F, DI2 R
DI3 F, DI4R
DI5 F, DI6 R
KEYPAD
COMM.CW
PARAM 10.04
10.02
EXT2 STRT/STP/DIR
NOT SEL
DI1 F, DI2 R
DI3 F, DI4R
DI5 F, DI6 R
KEYPAD
COMM.CW
PARAM 10.05
10.03
REF DIRECTION
FORWARD
REVERSE
REQUEST
Description
The sources for external start, stop and direction control
Defines the connections and the source of the Start, Stop and Direction
commands for external control location 1 (EXT1).
Note: In M/F configuration, EXT2 should be used for M/F mode and EXT1 for
stand-alone mode.
No Start, Stop and Direction command source.
Start, Stop and Direction commands through digital inputs DI1 and DI2.
DI1
DI2
Operation
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop
Note: Parameter
10.03
REF DIRECTION must be REQUEST.
Start, Stop and Direction commands through digital inputs DI3 and DI4.
See selection DI1 F, DI2 R.
Start, Stop and Direction commands through digital inputs DI5 and DI6.
See selection DI1 F, DI2 R.
Control panel. To control the direction, parameter
be REQUEST.
Fieldbus Control Word. See
Source selected with parameter
used for joystick controls when the joystick reference is used for deciding the
direction.
Defines the connections and the source of the Start, Stop and Direction
commands for external control location 2 (EXT2).
Note: In M/F configuration, EXT2 should be used for M/F mode and EXT1 for
stand-alone mode.
See parameter
10.01
EXT1 STRT/STP/DIR.
See parameter
10.01
EXT1 STRT/STP/DIR.
See parameter
10.01
EXT1 STRT/STP/DIR.
See parameter
10.01
EXT1 STRT/STP/DIR.
See parameter
10.01
EXT1 STRT/STP/DIR.
See parameter
10.01
EXT1 STRT/STP/DIR.
Source selected
with10.05
joystick controls when the joystick reference is used for deciding the direction.
Enables the control of rotation direction of the motor, or fixes the direction.
Fixed to forward
Fixed to reverse
Direction of rotation control allowed
10.03
03.01 MAIN CONTROL WORD
10.04
EXT1 STRT PTR. This selection can be
EXT2 STRT PTR.This selection can be used for
FbEq
1
2
3
4
REF DIRECTION must
5
bit 3 on page 250. 6
7
1
2
3
4
5
6
7
1
2
3
Actual signals and parameters