Technical data
10.2 Technical data, Power Modules
Current derating depending on the pulse frequency
Article number
6SL3210-1PE11-8❒L1
6SL3210-1PE12-3❒L1
6SL3211-1PE13-2❒L1
6SL3210-1PE14-3❒L1
6SL3210-1PE16-1❒L1
6SL321❒-1PE18-0❒L1
6SL3210-1PE21-1❒L0
6SL3210-1PE21-4❒L0
6SL321❒-1PE21-8❒L0
6SL3210-1PE22-7❒L0
6SL321❒-1PE23-3❒L0
6SL3210-1PE23-8❒L0
6SL3210-1PE24-5❒L0
6SL3210-1PE26-0❒L0
6SL3210-1PE27-5❒L0
6SL3210-1PE28-8❒L0
6SL3210-1PE31-1❒L0
The permissible motor cable length also depends on the cable type and the selected pulse fre-
1)
quency.
402
LO base load output current for a pulse frequency of ...
4 kHz
6 kHz
8 kHz
1.7
1.4
1.2
2.2
1.9
1.5
3.1
2.6
2.2
4.1
3.5
2.9
5.9
5.0
4.1
7.7
6.5
5.4
10.2
8.7
7.1
13.2
11.2
9.2
18.0
15.3
12.6
26.0
22.1
18.2
32.0
27.2
22.4
38
32.3
26.6
45
38.3
31.5
60
51.0
42.0
75
63.8
52.5
90
76.5
63.0
110
93.5
77.0
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
for 400 V devices
1)
[A]
10 kHz
12 kHz
1.0
0.9
1.3
1.1
1.9
1.6
2.5
2.1
3.5
3.0
4.6
3.9
6.1
5.1
7.9
6.6
10.8
9.0
15.6
13.0
19.2
16
22.8
19.0
27.0
22.5
36.0
30.0
45.0
37.5
54.0
45.0
66.0
55.0
Converter with CU230P-2 Control Units