High Frequency Modules
4.4 HF Sine Filter Module
4.4.3.2

X21 inputs for temperature monitoring

Table 4- 15
X21 inputs for temperature monitoring
Terminal
1
2
3
4
Type: Screw terminal 1 (Page 172)
Max. connectable cross-section: 1.5 mm
Connect the terminals to transfer the temperature signals
The HF line-up does not function without the X21 terminals being connected. Therefore, it is
absolutely necessary that the following terminals are connected with one another to transfer
the temperature signals from the HF Choke Module to the HF Damping Module:
● X21.1 and X21.2 on the HF Choke Module with X21.1 and X21.2 on the HF Damping
Module
● X21.3 and X21.4 on the HF Choke Module with X21.3 and X21.4 on the HF Damping
Module
Use shielded signal cables and connect the cable shields to the supplied shield terminal.
4.4.3.3

X200-X203 DRIVE-CLiQ interfaces

Table 4- 16
X200-X203 DRIVE-CLiQ interfaces
Pin
1
2
3
4
5
6
7
8
A
B
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
50
Function
+ Temp
- Temp
+ Temp
- Temp
2
Name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical data
Temperature HF Choke Module analog:
KTY84-1C130 temperature sensor
Temperature Choke Module digital:
Bimetallic switch
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3