Redundant Aus, Voting By Sca-Rs, Distance Higher Than 200 M - Siemens SICAM AK Manual

Rtus. redundancy,
Table of Contents

Advertisement

1.3.1.3

Redundant AUs, Voting by SCA-RS, Distance higher than 200 m

Implemented with the third party product MOXA Nport Server:
UN 1373-1B
SCA-RS Voter
Cable
CM-1820
TB cable
length 15 m
Cable
Patch cable
Cable 
FO-cable indoor
1000 DUP (max. 15 m)
2 x Connector
UN 1373-1B
Ethernet
Cable 
High speed link
FO, max. length 200 m
Automation unit
SICAM AK
to the remote
peripheral elements
to the slaves
SCA-RS is connected to SICAM AK via the
socket connector SYS-IO on the SICAM AK
Redundancy synchronization of functional
diagrams and periphery is carried out via free
selectable communication (Ethernet preferred,
select transfer as fast as possible); a separate
interface is recommended
The electrical connection between Ethernet
and SICAM RTUs component or between
Ethernet and MOXA-Server can be up to
100 m
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
MOXA NPort IA5150
with power supply
1
HSA 50S24-P
2
2
see the sections "Redundant Basic System Elements"
and
"Redundant AUs in ring configurations"
and
"Redundant AUs in star configurations"
Unrestricted
Redundancy via SCA-RS
back view CM-2816
4
HSA 50S24-P
UN 1373-1B
2
1
redundancy synchronization
preferred via Ethernet
The protocol element for redundancy
synchronization must not be placed on the
M-CPU but should be necessarily situated
on the synchronized C-CPUs
In this configuration only redundant
periphery is possible
ATTENTION: Time-critical applications are
not possible in the FUD; minimal cycle time:
1 ms
The MOXA Server can be supplied by the
Power Supply HSA 50S24-P from MTM
Power (item number: MTM+HSA50S24-P)
CM-1820 TB cable
Connector
UN1373-1B
MOXA NPort IA5150
with power supply
IEC 69870-5-104
2
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents