The following parameters can be set:
IP address of the current voter
Subnet Mask of the current voter
Default Router
IP address of the other voter
IP address of SICAM AK A and SICAM AK B
IP address of the NTP server
Maximal response time of SICAM AK
Availability of a key switch module (selection Yes/No)
NTP Server
If a NTP server is not present in the SICAM AK Redundancy system, you must configure the
IP address as 0.0.0.0.
For synchronizing the local time when a NTP server is connected to the system, you must set
the
Time Zone
SICAM AK Response Timeout
The parameter
from SICAM AK.
It is recommended to set the
the substation automation system.
The preferred response time is from 100 ms to 5 s. The default time is 2 s.
2.4.2.3.2

Address configuration according to IEC 60870-5-104

The addresses of the involved automation systems are set in the menu Parameters under
the item Address information.
"Voter to SICAM AK A" and "Voter to SICAM AK B" represents the Control message of the
system. These messages define the decisions of Voter and to make SICAM AK as active and
passive. They contain the status information of the voter, as for instance the position of the
key switch.
"SICAM AK A to Voter" and "SICAM AK B to Voter" represents the Return information
message of the system. These messages define the active/passive status of SICAM AK and
the priority of the errors.
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
in menu Time Setting | Time zone.
defines the waiting time of CP-6010 to get a response
AK response timeout
AK response timeout
based on the network traffic existing in