SICAM AK Switchover Settings
This section describes exemplarily the engineering of the redundancy switchover in the
SICAM TOOLBOX II for the system SICAM AK.
2.5.1
Communication Settings
The following settings must be performed in order to set up the functionality of the redundancy
in both modes of operation ("global switchover", "line-by-line switchover").
2.5.1.1
System-Technical Settings
In both systems SICAM AK, select under the M-CPU the menu connection definition and
enter the IP address of the respective CP-6010.
Select the menu IP address and enter the IP addresses of the corresponding system
SICAM AK.
Select the menu 104 parameters and enter the IEC 60870-5-104 timeout values.
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Unrestricted
Redundancy via CP-6010