Siemens SINAMICS S120 Function Manual page 269

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

● Change password for the TM54F
– p0010 = 95 Commissioning mode.
– p10061 = Enter "Old TM54F Safety Password" (factory setting "0")
– p10062 = Enter "new password"
– p10063 = Acknowledge "new password"
– p0977 = 1; "Copy from RAM to ROM"
– The new and acknowledged safety password is valid immediately.
● Changing the password with Startdrive
– Click "Enter password" in the Startdrive secondary navigation.
– Enter the current password.
– Enter the new password.
– Enter the new password again.
– Click "Change password" to accept the new password.
● Resetting the password with Startdrive
– Click "Enter password" in the Startdrive secondary navigation.
– In the subsequent dialog, first enter the old password.
– Set the new password = 0.
– Click "Change password" to accept the new password.
– SINAMICS S120 responds with the message "Please change the password!"
– Close the message.
– In the "Change password" dialog box, then click the "Cancel" button.
– The password has now been reset to the default "0."
● If the safety password is no longer available, you can no longer change the safety
configuration. You then have the following options:
– To commission the SINAMICS S120 completely as new:
– To load another project into the drive (without a Safety password or with a known
– If neither option is acceptable to you, please contact "Technical Support" (see
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
- Restore the factory settings of the entire drive (Control Unit with all connected
drives/components).
- Commission the drive unit and the drives afresh.
- Commission Safety Integrated as new.
Safety password). This is possible without a password because this operation is the
same as complete new commissioning.
"Preface (Page 3)").
Commissioning
6.3 Handling the Safety password