Communication according to PROFIdrive
3.4 Acyclic communication
Error
Meaning
value
0x7C
Parameter %s [%s]: Write access
only in the commissioning state,
device download (de-
vice: p0009 = 29).
0x7D
Parameter %s [%s]: Write access
only in the commissioning state,
device parameter reset (de-
vice: p0009 = 30).
0x7E
Parameter %s [%s]: Write access
only in the commissioning state,
device ready (device: p0009 = 0).
0x7F
Parameter %s [%s]: Write access
only in the commissioning state,
device (device: p0009 not equal to 0).
0x81
Parameter %s [%s] must not be writ-
ten during download.
0x82
Transfer of master control is blocked
by BI: p0806.
0x83
Parameter %s [%s]: Requested BICO
interconnection not possible.
0x84
Parameter %s [%s]: Parameter
change inhibited
(refer to p0300, p0400, p0922)
0x85
Parameter %s [%s]: Access method
not defined.
0x87
Write job will not be executed.
0xC8
Below currently valid limit.
0xC9
Above currently valid limit.
0xCC
Write access not permitted.
58
Remark
–
–
–
–
–
–
BICO output does not supply float values. The BICO input,
however, requires a float value.
–
–
The write request is rejected because know-how protection
is active.
Modification request for a value that, although within "abso-
lute" limits, is below the currently valid lower limit.
Modification request for a value that, although within "abso-
lute" limits, is above the currently valid upper limit (e.g. gov-
erned by the current converter rating).
Write access is not permitted because an access code is not
available.
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
Additional
info
–
–
–
–
–
–
–
–
–
–
–
–
–
Communication