Communication Failure When Booting Or In Cyclic Operation - Siemens SINAMICS S120 Series Function Manual

Hide thumbs Also See for SINAMICS S120 Series:
Table of Contents

Advertisement

Communication via SINAMICS Link

8.5 Communication failure when booting or in cyclic operation

8.5
Communication failure when booting or in cyclic operation
If at least one sender does not correctly boot after commissioning or fails in cyclic operation,
then alarm A50005 is output to the other nodes: "Sender was not found on the SINAMICS
Link."
The message contains the number of the faulted node. After you have resolved the fault at
the node involved and the system has identified the node, the system automatically
withdraws the alarm.
If several nodes are involved, the message occurs a multiple number of times consecutively
with different node numbers. After you have resolved all of the faults, the system
automatically withdraws the alarm.
When a node fails in cyclic operation, in addition to alarm A50005, fault F08501 is output:
"COMM BOARD: Monitoring time, process data expired"
At node 1, fault F08501 is not triggered. This node should be used for specifying setpoint
values to other nodes.
8.6
Examples: Transmission times for SINAMICS Link
Example 1: Transmission times at a communication cycle of 1 ms
p2048 or p8848 = 1 ms
Example 2: Transmission times at a communication cycle of 4 ms
p2048 or p8848 = 4 ms
214
Bus cycle
Sync both
0.5
1.0
1.0
1.5
2.0
3.0
Bus cycle
Sync both
0.5
1.0
1.0
1.5
2.0
3.0
Transmission time
Sync send
Sync receive
1.5
1.3
2.1
2.1
3.6
3.1
Transmission time
Sync send
Sync receive
3.0
2.8
3.6
3.6
5.1
4.6
Function Manual, 12/2018, 6SL3097-5BD00-0BP0
Async both
1.6
2.2
2.8
Async both
4.6
5.2
5.8
Communication

Advertisement

Table of Contents
loading

Table of Contents