Communication via Ethernet/IP (EIP)

7.4 Configuring EIP via the onboard PROFINET X150 interface

7.4
Configuring EIP via the onboard PROFINET X150 interface
To communicate with a higher-level control via EIP, make the following settings for the
PROFINET interface at the CU320-2 PN:
1. With p2030 = 10, set the firmware version of "EtherNet/IP".
2. Set the IP address using p8921.
You can find the currently valid address in r8931.
3. Set the subnet mask using p8923.
You can find the currently valid subnet mask in r8933.
4. Set the standard gateway using p8922.
You can find the currently valid standard gateway in r8932.
5. Set the station name using p8920.
You can find the currently valid station name in r8930.
6. Select the setting "Save and activate configuration" as interface configuration using
p8925 = 2.
7. Save the data using command "Copy RAM to ROM".
Then switch off the drive power supply.
8. Carry out a POWER ON (switch off the Control Unit and switch on again).
Wait until all LEDs on the drive are dark before switching on. Your settings become active
after switching on.
Result:
You have configured the onboard PROFINET X150 interface of the drive for communication
via EIP .