Panasonic 2WAY Multi Technical & Service Manual page 153

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

Indoor Unit Status Display: No. 9 (Level 0) <  >
Displays of connected indoor unit status.
Also possible to activate forced thermostat-off settings for specifi c indoor units.
1) Indoor unit status display (Level 0)
Shows menu selected indoor unit status display.

2) Indoor unit thermostat status display (Level 1)
In the indoor unit display mode, pressing the SET (S007) key displays the indoor unit thermostat status.
(Example: No. 1 - 24 units connected) Note: 1 dot at lower right
Lit
: Thermostat on unit
Flashing : ● 1-sec. cycle fl ashing indicates thermostat-off unit numbers
● 0.5-sec. cycle fl ashing indicates forced thermostat-off status unit numbers
Display examples
No. 1 to 32 units connected
Note: 1 dot at lower right
1 to 12 units from upper left to upper right of vertical line
13 to 24 units from lower left to lower right of vertical line
25 to 30 units from top left to top right of horizontal line
31 units, 32 units from bottom left horizontal line
Operate the UP (S005) and DOWN (S006) keys.
No. 33 to 48 units connected
Note: 2 dots at lower right
33 to 44 units from upper left to upper right of vertical line
45 to 48 units from lower left to lower right of vertical line
V–34