Panasonic 2WAY Multi Technical & Service Manual page 130

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

5) Data setting operation (Level 2)
Setting start operation method
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
Setting confi rm operation method : After entering the setting start operation or setting change operation
Setting cancel operation method
The setting details will not change when pressing the HOME (S004) key for one second during setting item
select operation.)
Data setting operation is possible from items No. 0 to No. 8.
The following data is displayed.
Data
code
1 Engine operation time
2 Engine operation count
3 Starter operation time
4 Starter operation count
5 Current oil change time
6
7
8
9
A
b
c
d
E Clutch on time
F Clutch on count
G Clutch 2 on time
H Clutch 2 on count
i
J
K
L
n
o
P Oil error time
q
10 Engine revolution setting
11 Engine revolutions
12 Compressor inlet pressure
13 Compressor outlet pressure
14 Compressor inlet temperature
15 Compressor outlet temperature
Outdoor unit heat exchange inlet
16
temperature
: Press the SET (S007) key for one second in the setting data code select
mode.
This activates the forced setting in progress display. (TEST/WARNING
LED light)
and DOWN (S006) keys make it possible to change the setting details
of the selected setting categories.
completed, press the SET (S007) key for one second.
This cancels the forced setting in progress display, making it possible to
once again enter setting item selection operation mode.
(TEST/WARNING LED off)
: Press the HOME (S004) key for one second before confi rming setting.
This returns operation to normal. (TEST/WARNING LED off)
Measurement item
Data name
V–11
Display
examples
Unit
Hrs

Times

Seconds

Times

Hrs

Hrs

Times

Hrs

Times

Hrs

-1
min

-1
min

MPa

MPa

°C

°C

°C

Standard operation data
During cooling
During heating
operations
operations
600~2200
600~2200
0.60~0.90
0.30~1.10
2.30~3.20
2.40~3.30
5~30
0~30
70~110
80~110
30~50
-5~10