Chapter 9. Diagnostics
9.5.8

Module Fault (Category 8)

The fault category Module Fault has one fault type, headend fault, and eight fault descriptions. This
fault category does not provide fault extra data. The default fault action for this category is
Diagnostic.
08 hex, Configuration Memory Failure
The GBC generates this error when it detects a failure in a Genius block's EEPROM or NVRAM.
Correction
Replace the Genius block's electronics module.
20 hex/32 decimal, Calibration Memory Failure
The GBC generates this error when it detects a failure in a Genius block's calibration memory.
Correction
Replace the Genius block's electronics module.
40 hex/64 decimal, Shared RAM Fault
The GBC generates this error when it detects an error in a Genius block's shared RAM.
Correction
Replace the Genius block's electronics module.
80 hex/128 decimal, Module Fault
An internal failure has been detected in a module.
Correction
Replace the affected module.
81 hex/129 decimal, Watchdog Timeout
The CPU generates this error when it detects that an input module watchdog timer has expired.
Correction
Replace the input module.
84 hex/132 decimal, Output Fuse Blown
The CPU generates this error when it detects a blown fuse on an output module.
Correction
1) Determine and repair the cause of the fuse blowing, and replace the fuse.
2) Replace the module.
436
PACSystems* RX7i, RX3i and RSTi-EP CPU Programmer's Reference Manual