Svc_Req 19: Set Run Enable/Disable - GE PACSystems RX7i Cpu Programmer's Reference Manual

Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

Chapter 6. Service Request Function

6.20 SVC_REQ 19: Set Run Enable/Disable

Use SVC_REQ 19 to permit the LD program to control the RUN mode of the CPU.
The parameter passed indicates which function to perform. The OK output is turned ON if the
function executes successfully. It is set OFF if the requested operation is not SET RUN DISABLE mode
(1) or SET RUN ENABLE mode (2).
The parameter block is an input parameter block only with this format:
Address 1 = SET RUN DISABLE mode
2 = SET RUN ENABLE mode
SVC_REQ 19 Example
When input %I00157 transitions to on, the RUN DISABLE mode is set. When the SVC_REQ function
successfully executes, coil %Q00157 is turned on. When %Q00157 is on and register %R00099 is
greater than zero, the mode is changed to RUN ENABLE mode. When the SVC_REQ successfully
executes, coil %Q00157 is turned off.
GFK-2950C
February 2018
309