Operating Instructions Fire alarm system EBL512, V2.7.x

EBL512 settings download

EBL512 settings are normally factory downloaded in the EBL512
control unit before the delivery. It is however, possible to download
the following on site:
The number of addresses (max. loop units)
Serial number (normally not changed)
Date (normally not changed)
Adhesive type (Type 1 = "old", Type 2 = "new"; acc. to EN54)
If you wish to download new EBL512 settings, a PC and Win512 are
used. Before download, the PC has to be connected to the "D"
connector J1 in the control unit main board 1556 in question.
1. Start Win512. In the "Tools" menu open the "EBL512 settings"
dialog box.
2. Set the c.i.e. in "Bootstrap mode", i.e. set jumper "JP1 (BOOT)" in
position on the main board 1556.
3. Do a reset/restart, i.e. set jumper "JP4 (RESET)" in position
momentarily (approx. 1 second).
4. The buzzer will now sound intermittent and LED "LD101" starts
84
blinking
, indicating that the control unit is in "Bootstrap mode".
5. In the "Win512 settings" dialog box, click "Read". The buzzer
will be silenced, the actual settings shown and in the Win512 log
view will be shown: "System information has been uploaded."
6. Write the new settings in the fields respectively.
7. Do like 3 & 4 above. Click "Download". The buzzer will be
silenced and a "Win512" box will be displayed. Click "OK".
NOTE! If "Max. loop units" are changed, a "Please enter your
password" dialog box will be shown.
8. When the download is ready, in the Win512 log view it will be
shown: "System information has been downloaded".
9. Read, see 3, 4 & 5 above, to verify the new settings.
10. Remove jumper "JP1 (BOOT)". Do a reset/restart, see 3 above.
Regarding the reset/restart, see chapter "Restart", page 88.
Follow the same procedure in each control unit.

Control Units in a TLON network

All control units connected to a TLON network have the same
convention (via the SSD download) but the number of addresses
(max. loop units) and the language can vary if required.
86
To change the "Max. loop units", a separate password for download is
required. This password is in conjunction with a "Key" (eight digits) and is
available from the producer if you are authorized. The Key is shown in
Win512.
87
86
86