Operating Instructions Fire alarm system EBL512, V2.7.x
Blown fuse (F1 or F5) on the output unit rectifier p.c.b.
Battery charging is turned off, i.e. the total current consumption
incl. the battery charging current is too high (> 4.5 A). Valid
for the Ext. power supply unit 3366.
"/Mains OK" output in 3366 is high.
"/Mains OK" input in 3364 is high.
FAULT: Multiple faults COM-loop x, CU xx
Break (cut-off) / short-circuit in more than one segment on the COM
loop x in control unit no. xx.
FAULT: No connection to MMI board, CU xx
This fault message cannot be shown in the control unit's display, only
via Win512 version 2.7.x, via Web-server and in other control units in
the system.
Fault in the MMI board 5011 software or the MMI board. Check the
cable between the boards. This is a very serious fault. Call for service
personnel/engineer immediately.
FAULT: No reply expansion board x, CU xx
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583, mounted in the control
unit no. xx.
EBL512 G3 cannot communicate with the board. Check /
change the address. Check the cables / connections.
Check if the Main board fuse F13 is broken. Fuse: T4A L
250V (TR5).
FAULT: No reply board x, loop x, CU xx
This is valid for the I/O Matrix board (4582) no. x, connected on
COM loop x in the control unit no. xx.
Check the board's address, i.e. the I/O Matrix board no.
(Jumpers JP1 and JP2 on the board).
Check if the board is disconnected from the loop.
FAULT: No reply techn.no. xxxxxx
69