Operating Instructions Fire alarm system EBL512, V2.7.x
Activate address in alarm mode (H8/S9)
One alarm point (address), not a whole zone, can be set in alarm
status. The built-in LED in the alarm point (detector) will be turned
on to indicate the alarm. Among other applications, this function is
used for installations on ships.
NOTE! All outputs, standard and programmable, which would have
been activated by a real fire alarm from the same alarm point, will be
activated by this manual alarm as well.
Alarm activated via this menu will be automatically reset after one
hour.
Text in display
Activate address in alarm mode
Select zone: 000
Select zone: 123
POINT: 123-45
User definable text, if programmed
Select zone: 000
Select zone: 012
POINT: 123-45
LAST: 012-34
User definable text, if programmed
ACCEPT?
address: 00
ACCEPT?
address: 45
ACCEPT?
No.: 001
address: 00
ACCEPT?
address: 34
ACCEPT?
No.: 002
150
Comments
According to chapter
"Access code for
maintenance", see page
141.
S9
Press "A" to accept / start
the fire alarm.
Normal fire alarm
presentation in the control
unit(s) / FBPs display.
If more alarm points have
to be set in alarm status,
press "Return" to select
another zone - address and
continue as above.
Press "A" to accept / start
the fire alarm.