28.4
Action
"Access"
Scroll to menu A3
"A"
"A"
or
"1", "A"
"A"
"Return"
Rev: -
Direction for communication on COM-/BS4-
loop (H5/A3)
NOTE! If the selected control unit number is an EBL512 G3 unit in
a mixed system the function is different, see Operating Instructions
(MEW01473) for the EBL512 G3 system.
The communication direction is normally automatically changed
every minute, to ensure that the wires are okay all the way. To make
trouble shooting easier (e.g. during the commissioning) it is possible
to lock the communication on a COM or BS4
FAULT: No reply techn. no. xxxxxx
reduced delay time. This function can be used to list all technical
numbers "behind" a loop cut-off.
NOTE! Loop cut-off and short-circuit faults cannot be generated,
since they require communication in both directions at the same time.
The locking only works as long as you see the text:
COM-loop is currently communicating in A-direction
B-direction)
alternatively
(
When you log out or if you are automatically logged out (after 60
min.), the communication will start in the A-direction.
Text in display
Direction for communication on
COM-/BS4-loop
Select type of loop: 0 (0=COM, 1=BS4)
Lock COM-loop: 0 (0-3)
Control unit: 00
Lock direction on BS4-loop: 0,
Board: 0, Control unit: 00
COM-loop is currently communicating in
A-direction
See NOTE! above.
(When you select a BS4 loop, the text in this menu will still be
COM loop).
Direction for communication on
COM-/BS4-loop
108
An Autronica interface board 1584 is required in the control unit.
Operating Instructions Fire alarm system EBL512, V2.7.x
in menu A3.
ACCEPT? A3
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? A3
129
108
loop in one direction.
will be generated with a
Comments
According to chapter
"Access code for service
(H5)", see page 126.
Press "A" or "1" and "A"
to accept.
Write loop number (board
number) and control unit
number. Press "A" to
accept.
(Maybe the B-direction is
shown instead.).
Press "A" to change
direction. Press "Return"
to finish the locking (and
return to menu A3).
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.