Activate Address In Alarm Mode (H8/S6) - Panasonic EBL512 G3 Operating Instructions Manual

Hide thumbs Also See for EBL512 G3:
Table of Contents

Advertisement

34.6. ACTIVATE ADDRESS IN ALARM MODE (H8/S6)

One alarm point (zone-address), not a whole zone, can be set in alarm. It will be presented as a fire alarm, the built-in LED in the
alarm point (for example a detector) will be turned on and all outputs, standard and programmable, which would have been activat-
ed by a normal fire alarm from the same alarm point will be activated.
In all other control units in the system the alarm will be presented as a Test mode alarm.
If a real fire alarm occurs, the "Test mode alarm" will be automatically reset by the actual fire alarm.
A detector programmed for "Quiet alarm" will activate a Quiet test alarm instead of a fire alarm.
a) Log on to the c.i.e.
b) Navigate to menu S6.
c) Write the wanted zone and address.
(press ↵)
Select zone: 123 address: 45
d) Press
to start the alarm mode of this zone address.
First alarm: 123-45
Latest alarm: 123-45
-----------------------------------------------------------------------
(press ↵)
Select zone: 123 address: 45
RESET
e) Press "Reset" to reset the fire alarm.
f) Press ESC to leave this menu.
This manually activated fire alarm will be presented as "Test mode alarm" in all control unit displays and all display units and indicat-
ed by the LEDs "Fire" and "Fire brigade tx".
1 zone in alarm
122

Advertisement

Table of Contents
loading

Table of Contents